• Electric Automatic Reactive Voltage Regulator
  • Electric Automatic Reactive Voltage Regulator
  • Electric Automatic Reactive Voltage Regulator
  • Electric Automatic Reactive Voltage Regulator
  • Electric Automatic Reactive Voltage Regulator

Electric Automatic Reactive Voltage Regulator

Type: Automatic Reactive Voltage Regulator
Item: Reactive Power Compensation/Automatic Reactive Vol
Transport Package: Wooden Case
Specification: type tested
Trademark: Farady
Origin: Zhejiang
Customization:

Contact Supplier

360° Virtual Tour

Diamond Member Since 2015

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
KVX
HS Code
9030899090
Production Capacity
5000unit/Year

Product Description

+++++General

With the rapid development of national economy and the improvement of people's living standard, people's demand for electricity is increasing day by day. It puts forward higher request to the reliability and quality of power supply. However. Distribution network construction is seriously lagging behind, the grid is weak, facilities aging, line length, small diameter, most of the power distribution transformers are high energy consumption, network loss is increasingly prominent.
 Voltage quality is one of the important indicators to measure the power quality of power system, and its quality depends on whether the power flow distribution is reasonable or not. Due to the increasing load and the power supply, the network structure of the power system not only changes the network structure of the power system, but also changes the power distribution of the system. May even cause serious problems in local areas, the situation is generally low voltage level. This is not only related to the power system to provide users with power quality issues, but also directly affect the safety and economic operation of the power grid. At the same time, it is necessary to consider the power factor and voltage of the network, because the network power factor and voltage reduction will make the electrical equipment is not fully utilized, thereby reducing the transmission capacity of the network, and cause loss increase.

 Reactive power compensation benefits
l  Improves system power factor
l  Reduces network losses
l  Avoid penalty charges from utilities for excessive consumption of reactive power
l  Reduces cost and generates higher revenue for the customer
l  Increases system capacity and saves cost on    new installations
l  Improves voltage regulation in the network
l  Increases power availability

+++++Product scope

Rated voltage:6kV to 35kV
(30kV-230kV Power transformer substation)
Rated frequency:50Hz, 60Hz
Rated reactive power capacity:50kvar-36000kvar
Environment temperature:-45ºC-+55ºC
Altitude:<4500m
Compensation taps:9 to 25 taps
Voltage regulation range:50%Un-100%Un
Regulation reactive power range:25%Qn-100%Qn
Impedance:<2.0%
Controller system:DWK controller
 
 
+++++ Working principle
 
The work principle of Farady regulating type capacitors is that: Connect all the capacitors to the electric network with voltage regulator ,the output reactive power will be adjust by voltage regulator, refer to the capacitor output power formula: Qc=(U/Un)²Qn.


The set of equipment is made up by following equipments:
1. Load break switch
2. Insolating switch
3. Voltage regulator
4. Intelligent controller
5. Capacitors
6. Lighting arrester
7. Metering CT, PT
Assuming that the nominal capacitance of the capacitor is Qn , the connected voltage regulator regulation range is 50%Un-100%Un, so refer to the formula Qc=(U/Un)²Qn
,voltage regulator is designed with 9 taps tap changer to change the network voltage, see figure 2 , the output reactive power in every regulator position 


+++++ Advantages
 
The traditional way of reactive power compensation is changing the quantity of capacitors to adjust output reactive power, change method is usually switch or contactor, will result in following hazards
1. The conventional reactive power compensation method has a large compensation capacity and the adjustment is not flexible, it will lead to the compensation is not suitable , often appear over and not enough.
2.The capacitor switching can cause over-voltage and inrush current, and it will seriously affect and reduce the service life of the switch.
3.When the capacitor is switched on, as the capacitor will charged and discharged, when it need to switch on again, which affects the speed of the switching..
According to the above problems, o company developed the FLYK type reactive power compensation device, has the following advantages:

1.Energy conservation: Farady voltage regulating type capacitors will change the output reactive power by regulating voltage on capacitors, so that the reactive power can be adjusted smoothly. Comparing with other method, it can ensure the capacitors in best condition, the energy saving effect is much better
2.Low cost:If the old power transformer substation need to reform, only need to add a voltage regulator between the circuit breaker and capacitors, the original circuit breakers, reactors, capacitors can be reuse, greatly reduce the cost of transformation
 3.Maintance Free:When traditional circuit breaker and contactor switching, switching devices and capacitors often damaged because of the above problems, result in high maintenance costs, using Farady devices, automatic control reactive power output, there is no potential risks of other equipments, greatly reducing maintenance and staff costs in power transformer substation 
 

Send your message to this supplier

*From:
*To:
avatar Mr. Benliao Zheng
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Contact Supplier

360° Virtual Tour

Diamond Member Since 2015

Suppliers with verified business licenses

Manufacturer/Factory
Registered Capital
108880000 RMB
Management System Certification
ISO 9001, ISO 14001